Structure of key bits in the peripheral input of the process data area

Auswahl Hilfen previous top next english version

Easy ProfibusEPB Functional DescriptionProcess data areaPeripheral input key field 0

 

In the peripheral input key field 0 you will find information about the functional keys of the operator interface that have been pressed, as well as about other bit functions.

Each time a function key is pressed, the corresponding key bit is set and remains set for the entire time the function key remains pressed.

Please note that due to the cycle times there might be a delay in setting and resetting these bits.

Additional bit setting functions can/will be executed.

 

Peripheral input Key field 0





Start address +01

Key /Function

valid for

used for / as

Comment

Bit 00

CUP

ET-65, ET-75, ET-125

MT-65, MT-125

System operation / key

Bit for the Cursor Up key is set

Bit 01

CUD

ET-65, ET-75, ET-125

MT-65, MT-125

System operation / key

Bit for Cursor Down key is set

Bit 02

CUL

ET-65, ET-75, ET-125

MT-65, MT-125

System operation / key

Bit for Cursor Left key is set

Bit 03

CUR

ET-65, ET-75, ET-125

MT-65, MT-125

System operation / key

Bit for Cursor Right key is set

Bit 04

ESC

ET-65, ET-75, ET-125

MT-65, MT-125

System operation / key

Bit of Escape (Clear) key is set

Bit 05

CR

ET-65, ET-75, ET-125

MT-65, MT-125

System operation / key

Bit of Enter key is set.

If a reader is connected and during a valid reading process this bit is set together with bit number 11.  *

Bit 06

 

ET-65, ET-75, ET-125

MT-65, MT-125

 

 

Bit 07

 

ET-65, ET-75, ET-125

MT-65, MT-125

 

 

Bit 08

 

ET-65, ET-75, ET-125

MT-65, MT-125

 

 

Bit 09

 

ET-65, ET-75, ET-125

MT-65, MT-125

 

 

Bit 10

Life bit

ET-65, ET-75, ET-125

MT-65, MT-125

Reader system function

ONLY for Mifare Readers !

Bit 11

Input via reader unit

ET-65, ET-75, ET-125

MT-65, MT-125

Reader system function

If a reader is connected and during a valid reading process this bit is set together with bit number 5.  *

Bit 12

Info

ET-65, ET-75, ET-125

MT-65, MT-125

System operation / key

Bit of Info key is set.

Bit 13

Trigger bit

ET-65, ET-75, ET-125

MT-65, MT-125

System function

The trigger bit is also set each time a key is pressed.

Bit 14

Histogram full

ET-65, ET-75, ET-125

MT-65, MT-125

System function

This bit is set as soon as the histogram memory is full (ring buffer)

Bit 15

Pass bit

ET-65, ET-75, ET-125

MT-65, MT-125

System function

The pass bit is set by the operator interface and can be used to monitor communication.

 