Error 302 driver-dependent

Auswahl Hilfen previous top next english version

Error handlingError messages Falcon seriesError 302 driver-dependent

 

Driver

Error messages

Explanation, meaning

Remedy





Modbus RTU

(Master)

Station Nr xx failure

Failure of one communication partner (PLC)

Re-integrate communication partner (PLC) in communication





Modbus Slave

No key scanning by PLC

Keyboard register is scanned insufficiently or not at all by PLC

Scan keyboard register, decrease scanning time (must be scanned periodically < 10s)





Fieldbus

 

Bus error

Communication OK, but operator interface not addressed

Check PLC communication and settings





S7-MPI

MPI initialisation error

MPI Box could not be initialized

Check MPI Box address and reset



Incorrect operator interface address

Enter correct operator interface address



Incorrect PLC address

Enter correct PLC address

 

 

<< return