Error handling ► Error messages Falcon series ► Error messages during start-up phase
Output text of error messages
at the operator interface
|
Explanation, meaning
|
Remedy
|
|
|
|
011:
Error! No Code Banks, Load New *
|
No valid driver in the Flash memory chips
|
Execute a system download
|
021:
Error! No System, Load System**
|
Faulty system tables within the Flash memory chips
|
Execute a system download
|
024:
Buffer Failure. Getting Flashdata
|
No RAM data available, default values are loaded
Discharge condensator (retainment < 5 days), RAM data cannot be stored
|
New set-up of system menu, store data in the Flash condensator and reload, switch on operator interface
|
025:
Flash Invalid. Getting Default Data
|
Configuration data in Flash is invalid, does not match driver, default values will be loaded
|
Adapt configuration data to driver and save to Flash
|
041:
Error! Barcode Controller
|
Barcode controller could not be initialized
|
Hardware defective, device must be repaired
|
056:
Error! Out of Memory.
|
Font memory area exceeded
|
Execute system download with "original" fonts
|
100:
Error! Flash not Empty
|
Flash memory chip cannot be overwritten
|
Hardware defective, device must be repaired
|
101:
Text/configuration memory full!
|
Text memory is full, project contains too many objects
|
Reduce project and download it again
|
* Following this alarm message the operator interface displays the following message:
"012: Waiting For System Programming"
and is now ready to receive the system data again, with the interface parameter settings 8, 1, even, 9600 Baud.
** Following this alarm message the operator interface displays the following message:
"012: Waiting For System Programming"
and is now ready to receive the system data again, with the interface parameter settings 8, 1, even, 19200 Baud.