Accessories ► Readers ► SK-300 ► Installation ► Base station at RS-485 ► X2 & X3 RS-485 Pinning
The RS422/RS-485 interface of the devices is provided at terminals 1-8 at the X2 and X3 terminal blocks. The signals have the following meaning:
Pin
|
Name
|
Definition
|
1
|
TxD-b
|
Data/Out - the data is sent from here. Negated signal
|
2
|
TxD-a
|
Data/Out - the data is received here.
|
3
|
RxD-b
|
Data/In, this is where the data is received. Negated signal
|
4
|
RxD-a
|
Data/In, this is where the data is received.
|
5
|
TxD-b'
|
Direct connection to TxD-b, required for the provision of an RS-485 bus.
|
6
|
TxD-a'
|
Direct connection to TxD-ab, required for the provision of an RS-485 bus.
|
7
|
RxD-b'
|
Direct connection to RTxD-b, required for the provision of an RS-485 bus.
|
8
|
RxD-a'
|
Direct connection to RTxD-a, required for the provision of an RS-485 bus.
|
|
Termination ET/MT-xx6, ET/MT-xx6-Fx/Tx
The S3 and S4 dip switches activate the bus termination resistors of the COM1 and the COM2 with an RS-422 or RS-485 connection.
Switch
|
Position
|
Interface
|
Function
|
S3-1
|
OFF
|
COM1
RS-422/485
|
No bus terminator resistor set
|
ON
|
Bus terminator resistor TxD line
|
S3-2
|
OFF
|
No bus terminator resistor set
|
ON
|
Bus terminator resistor RxD line
|
S4-1
|
OFF
|
COM2
RS-422/485
|
No bus terminator resistor set
|
ON
|
Bus terminator resistor TxD line
|
S4-2
|
OFF
|
No bus terminator resistor set
|
ON
|
Bus terminator resistor RxD line
|

|
If the HMIs communicate via MPI,
the S3-1 and S4-1 dip switches must NOT be set to ON.
Otherwise, communication between PLC and control system
cannot be guaranteed to run smoothly.
|
|
Termination ET/MT-xx6-A-...
The S3 dip switches activate the bus termination resistors of the COM1 with an RS-422 or RS-485 connection.
Switch
|
Position
|
Interface
|
Function
|
S3-1
|
OFF
|
COM1
RS-422/485
|
No bus terminator resistor set
|
ON
|
Bus terminator resistor TxD line
|
S3-2
|
OFF
|
No bus terminator resistor set
|
ON
|
Bus terminator resistor RxD line
|
S4-1
|
S4-2
|
S4-3
|
Interface
|
Keying
|
0
|
0
|
0
|
RS-422
|
Automatic keying
|
0
|
1
|
0
|
Keying always on
|
0
|
0
|
1
|
Keying enabled by SW
|
0
|
1
|
1
|
Driver inactive
|
1
|
0
|
0
|
RS-485
|
Automatic keying
|
1
|
1
|
0
|
Status not permitted
|
1
|
0
|
1
|
Keying enabled by SW
|
1
|
1
|
1
|
Driver inactive
|
Touch switched off:
|
S4-4 *
|
OFF
|
Touch *
|
Touch switched off
|
ON
|
Touch switched on
|
*
|
It is currently not possible to switch off the touch via the S4-4 dip switch.
|
|
|