X1 Power supply connection general

Vorheriges Oben Nächstes Helps selection copy topic address english version

AccessoriesReaderBoxElectrical installationX1 Power supply connection general

 

Warnhinweis

Warning

Explosion hazard, when connecting device in hazardous area !

If you have to connect the device in a hazardous area

you must use a suitable explosion-protected terminal box !

(for example a series 8118 terminal box).

 

 

Click to expand or collaps information.  24 VDC Class II

 

Hinweis

The output circuit cable is about 1.1 metres long and typically 3 x 1 mm² !

 

Wire

Signal name

Definition

1

+ VDC

Supply voltage 24VDC+

2

GND

Supply voltage ground 0VDC

Green/yellow

 

Equipotential bonding

 

See also:

Kapitelseite 24VDC from ET / MT - xx6, Anschlussbeschreibung der 24VDC - Variante an die Geräte der xx6 Serie

 

Click to expand or collaps information.  100 bis 240 VAC powerline

 

Hinweis

The output circuit cable is about 1.1 metres long and typically 3 x 1 mm² !

 

Wire

Signal name

Definition

1

L1

Supply voltage phase

2

N

Supply voltage neutral

PE

Earth

Protective earth

 

Warnhinweis

Re. *1),

Make sure you have the AC version

before connecting the ReaderBox to the mains !

 

See also:

Kapitelseite Connectors ReaderBox

Kapitelseite 24VDC of ET / MT - xx6

Kapitelseite Connection RS232 to ET/MT-xx6

Kapitelseite Connection RS232 to ET/MT-xx7

Kapitelseite Connection RS422 to ET/MT-xx6

 

 

<< back