X2 Connection RS232 to ET/MT-xx7

Vorheriges Oben Nächstes Helps selection copy topic address english version

AccessoriesReaderBoxElectrical installationX2 Connection RS232 to ET/MT-xx7

 

Inside junction box of the ET / MT-xx7:

ReaderBox_To_xx7

 

RS-232 connection detail:

ReaderBox_To_xx7_V24detail

 

Device name

 

ReaderBox-054-DC-RS232 *1

Connection

Data circuit

Cable

5 x 1 mm²

-

Designation

Open cable end X2

Terminal X97 (SER - RS-232)

View

Fgr_ReaderBox_X3_Cable

Lieferzustand:

alle Adern schwarz und nummeriert.

Fgr_xx7_X97_connector

1

5

Assignments / connections (wire / pin)

Wire *2

Signal

Pin

Signal

2


N.V.

1

TxD

1


TxD

2

RxD

4


N.V.

3

RTS/

5

Green / Yellow

N.V.

4

CTS/

3


GND

5

GND

 

*1)

DC = ReaderBox with 24 VDC connection.

AC = ReaderBox with 100 to 240 VAC connection.

*2)

The data cable X2 is multi-core cables. Any unused wires are not assigned in the ReaderBox.

 

The unused wires of X2 must be isolated according to applicable regulations. This may be by means of double isolation and mechanical fixing by shrink sleeving or vulcanisation. The shrink sleeving or the vulcanisation must be suitable for at least 500 V and be within the temperature parameters of the device. The shrink sleeving / vulcanisation must not be light blue. When the data cables are shortened, this must also be kept in mind.

 

See also:

Kapitelseite Connectors ReaderBox

Kapitelseite Power supply connection general

Kapitelseite 24VDC of ET / MT - xx6

Kapitelseite Connection RS232 to ET/MT-xx6

Kapitelseite Connection RS422 to ET/MT-xx6

 

 

<< back