Inside junction box of the ET / MT-xx6:

ReaderBox_To_xx6_RS232

 

RS-232 connection detail:

 

 

Device name

ReaderBox-...-DC(AC)-RS232*1

HMI ET-/MT-xx6

Connection

Data circuit

Cable

5 x 1 mm²

-

Designation

Open cable endX2

Terminal X2 (COM1 - RS-232)

View

Fgr_ReaderBox_X3_Cable

delivery state:

all wires black and numbered..

Fgr_xx6_X2_connector

Assignments / connections (wire / pin)

Wire

Signal

Pin

Signal

2

Blue *

Not used *

9

TxD

1

Brown

TxD

10

RxD

4

Grey *

Not used **

11

RTS/

5

Green / Yellow *

Not used **

12

CTS/

3

Black

GND

13

GND

 

*1)

DC = ReaderBox with 24 VDC connection.

AC = ReaderBox with 100 to 240 VAC connection.

*2)

The data cable X2 is multi-core cables. Any unused wires are not assigned in the ReaderBox.

 

The unused wires of X2 must be isolated according to applicable regulations. This may be by means of double isolation and mechanical fixing by shrink sleeving or vulcanisation. The shrink sleeving or the vulcanisation must be suitable for at least 500 V and be within the temperature parameters of the device. The shrink sleeving / vulcanisation must not be light blue. When the data cables are shortened, this must also be kept in mind.

 

See also: