to PS2 of the xT-xx6 series

Vorheriges Oben Nächstes Helps selection copy topic address english version

AccessoriesJoystick JSiElectrical installationto PS2 of the xT-xx6 series

 

Warnhinweis

Warning

Explosion hazard, when connecting device in hazardous area !

If you have to connect the device in a hazardous area

you must use a suitable explosion-protected terminal box !

(for example a series 8118 terminal box).

 

Add a label to the switch boxes like follow:

 

Warnhinweis

Caution

Explosion hazard, Do not open !

Isolate supply and all Ex e and Ex i circuits, wait 25 minutes before opening switch boxes or connection !

 

Cable

HMI-Device

 

 

Fgr_TBi_JSi_Cable

 

Wire-

colour

Signal

Pin

X9

Yellow

VCC

1

Brown

MSDAT

4

White

MSCLK

5

Green

GND

6

Green/ Yellow

Shield

PE

 

Connection to X9 detailed:

Fgr_JSi_X9_Connect

 

 