In principle, fitters and operators have to observe the national installation directives and/or those superceding them.
Alternative ways to connect the cable screen are available for interference but they must conform to national installation directives and/or those superceding them.
|
Connection detailed
|
Shield connection terminal detailed
|
Terminal
cable shield
|

|
|
system’s equipotential bonding
in safety area
|
Connector threaded bolt
at Device (Ex area)
|
|
The Ex-e connection box has a screen connection rail for the alternative screen connection solution. In this case, the cable screening can be extended by a short wire (minimum diameter 1.5mm²) and connected to the clamping screws.
This equipotential bonding connection part is, as mentioned above, internally connected with the GND supply cable (X1 pins 3 and 4).
The ET-/MT-xx6’s equipotential bonding (6mm threaded bolt) must be connected to the system’s equipotential bonding (see illustration above).
Connection detail for electrical bonding (recommended)
|
Explanation
|

|
1.Enclosure HMI 2.Washer (2x) 3.Tooth lockwashers 4.Washer spring 5.Nut 6.Threaded bolt 7.Cable lug with eye |
|
Detail shield connection in Rev. 3:

For Rev. 1 and 2 devices:

|
equipotential bonding terminal
|
|
Please note the descriptions for each connection – they contain all details required for the individual connection (twisting, shielding, etc.)
|
|
|