Connectors DSPq

Vorheriges Oben Nächstes Helps selection copy topic address english version

AccessoriesPower supply DSPq-120-24Electrical installationConnectors DSPq

 

The DSPq-120-24-block devices are fitted with two fixed connection cables. The input circuit is connected via a 3 x 1 mm² and the output circuit is connected via a 2 x 1.5 mm² cable. Both cables must be connected to a suitable, separate terminal box.

 

Warnhinweis

Danger

Danger of electrostatic sparks

Both connection cables must be positioned in such a way that there is no electrostatic charge which may result in a propagating brush discharge !

 

 

PA-connector

M5      

all drillings

Ø 4,5 mm

Fgr_DSPs_TopView

output circuit

input circuit

 

Connections details:

 

input circuit


Fgr_DSPs_ConDetailed

L1 or + VDC (Braun)

Neutral or DC-Ground (Blue)

Protective earth (yellow/Green)

+24 VDC (1)

Ground (2)


output circuit


 

See also:

Kapitelseite Function, Beschreibung der Gerätefunktion und -typen

Kapitelseite Connect mains power, Versorgung der ReaderBox mit AC oder DC allgemein

Kapitelseite 24VDC von ET / MT - xx6, 24 Volt Versorgung der ReaderBox an ET / MT-xx6

 

Connections, voltage supply:

 

Hinweis

The input circuit cable is 2 metres long !

 

Wire

Colour

Signal name

Definition

1

Brown

L1 or +VDC

Mains power Phase or +VDC

2

Blue

Neutral or Ground

Mains power Neutral or VDC - Ground

PE

Green/yellow

Earth

Protective earth

 

Connections, 24 VDC out:

 

Hinweis

The output circuit cable is 2 metres long  !

 

Wire

Colour

Signal name

Definition

1

Black

+ 24 VDC

Power supply output  +VDC

2

Black

GND

Power supply output VDC - ground

 