via twisted pair

Vorheriges Oben Nächstes Helps selection copy topic address english version

HMIs, human machine interfacesPanel PC, ET / MT - 4x7Electrical InstallationConnection ofHost or control systemsvia twisted pair

 

The data transfer from the operator terminal in the hazardous area to the PLC is via a CAT7 twisted pair copper cable.

 

Hinweis

The listed operating parameters require

the use of category 7 Ethernet cables.

 

Although Ethernet cables of other categories (e.g. category 5) can be used, ,

the operating parameters can no longer be guaranteed.

 

Cupper_to_ET_MT_xx7_2

 

2. Ethernet-Interface optional.

 

*A)

Connection rail for equipotential bonding (shield connection)

*B)

Exposed shield connection oft he Ethernet cable

 

Details connection of cable shield:

Fgr_ShieldConnect_xx7

 

Terminal

Pin

Definition / typcial cable colour

Connection

Degree of protection

X16

CAT7 1

Data

1

TRD0+

White / Orange

100BASE-TX

Ex-e

Ex-nA

2

TRD0-

Orange

3

TRD1+

White / Green

4

TRD1-

Green

5

TRD2+

White / Orange

2nd 100BASE-TX

only for option -2TX-

6

TRD2-

Orange

7

TRD3+

White / Green

8

TRD3-

Green

9

SHLD

Screen


 

Cable type:


Twisted Pair

CAT7 installation cable AWG 22

 

Copper direct connection:

 

PLC, PC

or Server

 

Device ET/MT-xx7

CuEthernet_Direkt_xx7

 

Twisted Pair CAT7

 

The Ethernet connection can be at any port of the network.

 

 

See also

Kapitelseite Terminal assignment

 

See also

Kapitelseite Ethernet Connection Information

 

 

<< back