Fgr_X5_CAN_Bus

 

HMI

 

CAN - Bus

X5

Twisted Pair cable according to ISO 11898

Zl = 108–132 Ohm

Signal

1 or 3

 

2 or 4

Fgr_CAN_Connect_Simple

Low

 

High


Shielding optional (recommended)


 

Principle of a CAN bus system:

Fgr_DaisyChainPrinzipal

All participants are aligned in a chain (daisy chain). The first and last participant are terminated by a resistor (120 Ohm).

Spur lines or star networks are permitted, but special attention must be paid to the characteristic impedance.

Mismatches may lead to reflections at the wire ends of each bus wire, which in turn may result in higher error rates during data transmission.

 