HMIs, human machine interfaces ► Thin Client ET/MT-5x6 ► Connection overview ET/MT-5x6... ► ET/MT-xx6-A-Fx/Tx-... rev. 3 ► Overview X1-X7
Connections table:
Terminal
|
Pin
|
Meaning
|
Connection
|
X1
|
1
|
Supply voltage +24V DC
|
Power supply
|
2
|
Supply voltage +24V DC
|
3
|
Power supply GND
|
4
|
Power supply GND
|
X2 *1
|
1
|
TxD-b
|
COM1 serial interface
RS-422/RS-485
|
2
|
TxD-a
|
3
|
RxD-b
|
4
|
RxD-a
|
5
|
TxD-b'
|
6
|
TxD-a'
|
7
|
RxD-b'
|
8
|
RxD-a'
|
9
|
TxD > Output
|
COM1 RS-232 serial DTE interface
|
10
|
RxD < Input
|
11
|
RTS > Output
|
12
|
CTS < Input
|
13
|
GND
|
X3
|
1
|
Line Out right
|
Audio Ex-e
|
2
|
GND
|
3
|
Line Out left
|
X4
|
|
USB interface, connection type A
|
USB0 Ex-i
|
X5
|
1
|
VCC
|
USB1 Ex-e
|
2
|
USB -
|
3
|
USB +
|
4
|
GND
|
X6
|
1
|
VCC
|
USB2 Ex-i
|
2
|
USB -
|
3
|
USB +
|
4
|
GND
|
5
|
GND (from Rev. 1 onwards)
|
X7
|
1
|
VCC
|
USB3 Ex-e
|
2
|
USB -
|
3
|
USB +
|
4
|
GND
|
|
*1)
|
Option, have to be ordered.
|

|
Please note that the COM interface may only be physically connected once!
Interconnection is provided either with a physical RS-232
or an RS-422/485 connection.
|

|
With HW Rev. 3, four independent USB ports have been implemented.
|
|
Related topics:
ET/MT-4x6-Fx/Tx, Overview X1-X7 ,Rev. 2
<< back
|