X2, RS-232, RS-422 und RS-485

Vorheriges Oben Nächstes Helps selection copy topic address english version

HMIs, human machine interfacesEagle ET/MT-3x6...Connection toX2, RS-232, RS-422 und RS-485

 

Terminal

Pin

Signal

Connection

X2 *1

1

TxD-b

COM1 serial interface

RS-422/RS-485

2

TxD-a

3

RxD-b

4

RxD-a

5

TxD-b'

6

TxD-a'

7

RxD-b'

8

RxD-a'

9

TxD > Output

COM1 RS-232 serial DTE interface

10

RxD < Input

11

RTS > Output

12

CTS < Input

13

GND

 

*1)

Option, must be ordered.

 

Hinweis

Please note that the COM interface may only be physically connected once !

 

Interconnection is provided either with a physical RS-232 or an RS-422/485 connection.

 

 

See also:

Kapitelseite Anschluss von, RS-232 an X2

Kapitelseite Anschluss von, RS-422 an X2

Kapitelseite Anschluss von, RS 485 an X2

 

 

<< back