via RS-422 at MPI bus

Vorheriges Oben Nächstes Helps selection copy topic address english version

HMIs, human machine interfacesEagle ET/MT-3x6...Connection ofControl systems / Servervia RS-422 an MPI-Bus

 

In the case of an ET-208 or ET/MT-3x6 with RS 442 interface, a connection to an MPI bus is established via the HMI-RS422 MPI box. Its main purpose is to adapt the RS 422 interface to the RS 485 bus system of the MPI interface. In the transport layer (layer 4), the MPI box uses the RK512 protocol, and at the connection level it uses the 3964/R procedure. For further information, for example on the parameterisation of the MPI box, please refer to the MPI box manual.

 

Connection of ET-2x8 or ET/MT-3x6 devices to the CPU 3xx and CPU 4xx PLCs by Siemens.

 

Click to expand or collaps object.Figure, Connecting to MPI-Box HMI-RS422:

ET / MT-3x6

MPI-Box

Control

RS422_MPI_2xx

hazardous area

safety area

 

 

Click to expand or collaps information.  Pinning, Cable to MPI-Box HMI-RS422:

 

X2 (COM1) / X3 (COM2)

Terminals

MPI box

9-pin Sub-D

 

X2_X3_CableToMPIBox_en

 

 

Click to expand or collaps information.   Table, Connecting of the MPI-interface:

PIN

Signal name

Definition

1

N.C.

Not connected

2

0V (M24V)

Data reference potential 0V (of +24V)

3

RxD / TxD-P

Data line B

4

RTS / AS

Request to Send

5

0V (M5V)

Data reference potential 0V (of +5V)

6

+5V

Voltage +5 V

7

+24V

Voltage +24 V

8

RxD / TxD-N

Data line A

9

RTS PG

Request to Send PG

 

 

Hinweis

The Eagle bus connection to the MPI bus is implemented with the bus connection plug attached to the MPI box in compliance with the installation regulations applicable to the MPI bus.

 

Hinweis

The MPI bus only needs the two A and B data lines to communicate with the PLC.

 

 

<< back