Ethernet Connection information

Vorheriges Oben Nächstes Helps selection copy topic address english version

HMIs, human machine interfacesEagle ET/MT-3x6...Connection InformationsEthernet Connection information

 

Devices of the ET/MT-xx6... series can be ordered with an optical fibre or copper Ethernet connection. Below is a description of the different versions:

 

Optical fibre:

 

Click to expand or collaps information.   ET/MT-xx6-Fx und ET/MT-xx6-A-Fx..

This interfaces provides an Ethernet connection for the HMI.

 

SC double

coupling

 

LWL_SC-In

SC double

plug

 

LWL-SC_DoppelStecker

The Ethernet connection is established via the 9721 interface converter, using a double plug SC-SC cable.

Kbl_VB-SC-SC

 

See also:

Kapitelseite Connection to Control systems, via Ethernet IP, Anschluss an die SPS

 

 

Click to expand or collaps information.   ET/MT-xx6-Fx 1. Generation

This interfaces provides an Ethernet connection for the HMI.

 

LC double coupling

 

Skz_LWL_LC-In

LC double plug

 

LWL-LC_DoppelStecker

The Ethernet connection is established via the SK-KJ1710 or the SK-KJ1740 interface converter, using the following cable:

MT-RJ plug

 

MT-RJ_Stecker

Kbl_VB-LC-MTRJ

 

The MT-RJ plug is used to connect the optical fibre cable to the SK-KJ1710 or the

SK-KJ1740 media converter.

 

cable type:

Multi-mode optical fibre cable (62.5 µm core cross section and 125 µm external cross section)

 

 

Copper:

 

Click to expand or collaps information.   ET/MT-xx6-A-Tx-.. and ET/MT-xx6-Tx

 

Cables connected to the Ethernet terminals (X11) must have a minimum cross section of 0.2 mm² (metric) (AWG 24).

Which cable cross sections are chosen should be decided on the basis of relevant regulations, such as DIN VDE 0298 . Factors that might require a larger cross section, such as current, increased temperatures, cable bundling, etc. must also be taken into account. Factors that might require a larger cross section, such as current, increased temperatures, cable bundling, etc. must also be taken into account.

 

Click to expand or collaps object.   Figure, Connection:

xT-xx6 Ethernet connection details


     X11 terminal

Ethernet 100Base TX

Cable shield fixation

ConX1_ConnectingPrinzipal2


Twist wire pairs

up to the terminal

Ethernet-Cable

Shield

 

Cable colour codingVB-TP-CAT5-Exe-RJ45-Patch:

 

Yellow

blue

White

Orange

 

Profinetkabel

 

Table colour coding Ethernet - cable:

 

MT/ET-xx6-Tx

 

Coding according by

X11 Pin

Function

VB-TP-CAT5-..

EIA/TIA-T568A

EIA/TIA-T568B

1

TxD +

Yellow

Grün / White

Orange / White

2

TxD -

Orange

Green

Orange

3

RxD +

White

Orange / White

Grün / White

4

RxD -

Blue

Orange

Green

 

Click to expand or collaps object.  Colour coding Ethernet, T568A und T568B:

EthernetkabelFarbcodierung

 

 

For more information, please refer to chapter cicon2 VB-TP-CAT5-Exe-RJ45-Patch of the cable descriptions.

 

cable type:

Twisted Pair cable at least 4 x 2 x 0.4-0.6 rigid or 4 x 2 x 0.27 - 0.5 flexible, recommended type: Cat-5

 

 