Ethernet Connection information

Vorheriges Oben Nächstes Helps selection copy topic address english version

HMIs, human machine interfacesET-208Electrical Installation ET-208Ethernet Connection information

 

Devices of the ET/MT-xx6... series can be ordered with an copper Ethernet connection.

 

Copper:

 

Cables connected to the Ethernet terminals (X11) must have a minimum cross section of 0.2 mm² (metric) (AWG 24).

Which cable cross sections are chosen should be decided on the basis of relevant regulations, such as DIN VDE 0298 . Factors that might require a larger cross section, such as current, increased temperatures, cable bundling, etc. must also be taken into account. Factors that might require a larger cross section, such as current, increased temperatures, cable bundling, etc. must also be taken into account.

 

Click to expand or collaps object.   Connection:

 

X5Ethrnt_e_Port

Cable colour codingVB-TP-CAT5-Exe-RJ45-Patch:

 

Yellow

blue

White

Orange

 

Profinetkabel

 

Table Ethernet cable colours:

 

ET-208-TX

 

Coding according by

X5 Pin

Function

VB-TP-CAT5-Exe-R45-Patch

EIA/TIA-T568A

EIA/TIA-T568B

1

RxD -

Blue

Orange

Green

2

RxD +

White

Orange / White

Green / White

3

TxD -

Orange

Grün

Orange

4

TxD +

Yellow

Grün / White

Orange / White

 

Click to expand or collaps object.  Colour coding Ethernet, T568A und T568B:

EthernetkabelFarbcodierung


 

For further information see cicon2 VB-TP-CAT5-Exe-RJ45-Patch of cable descripition.

 

See also:

Kapitelseite Connection at,Controls, via Ethernet IP, Connection to IPC

 

 

cable type:

Twisted Pair cable at least 4 x 2 x 0.4-0.6 rigid or 4 x 2 x 0.27 - 0.5 flexible, recommended type: Cat-5

 

 