Accessories ► Readers ► IDM160 ► Electrical Installation ► X1 & X2 connecting of ReaderBox
X1 & X2 to devices of the ET-208 Series
The power supply for the ET-208 series is connected to a suitable terminal block in the safe area.
24 VDC

|
The output circuit cable is about 1.1 metres long and typically 3 x 1 mm² !
|
Wire
|
Signal name
|
Definition
|
1
|
+ VDC
|
Supply voltage 24VDC+
|
2
|
GND
|
Supply voltage ground 0VDC
|
Green/yellow
|
|
Equipotential bonding
|
|
Power supply 100 to 240 VAC

|
The output circuit cable is about 1.1 metres long and typically 3 x 1 mm² !
|
Wire
|
Signal name
|
Definition
|
1
|
L1
|
Supply voltage phase
|
2
|
N
|
Supply voltage neutral
|
PE
|
Earth
|
Protective earth
|

|
Re. *1),
Make sure you have the AC version
before connecting the ReaderBox to the mains !
|
|
X2 via RS-422
Inside junction box of the ET / MT-208:


|
The X2 interface of the Readerbox
must be connected to interface X3 (COM2) of the ET/MT-208.
|
RS-422 connection detail:
Device name
|
ReaderBox-...-DC(AC)*1
|
Connection
|
Data circuit
|
Cable
|
5 x 1 mm²
|
-
|
Designation
|
Open cable end X2
|
Terminal X3 (COM2 - RS-422)
|
View
|

delivery state:
all wires black and numbered.
|

|
Assignments / connections
(wire / pin)
|
Wire
|
Signal
|
Pin
|
Signal
|
3
|
|
RxD-b
|
1
|
TxD-b
|
4
|
|
RxD-a
|
2
|
TxD-a
|
1
|
|
TxD-b
|
3
|
RxD-b
|
2
|
|
TxD-a
|
4
|
RxD-a
|
5
|
Green / Yellow
|
Not used
|
-
|
-
|
*1)
|
DC = ReaderBox with 24 VDC connection.
AC = ReaderBox with 100 to 240 VAC connection.
|
|

|
The blue wires of the X2 data circuit of the ReaderBox is not needed and must be cut off at the cable end !
|
|
X1 & X2 to devices of the ET-/MT-xx6 Series
X1 24 VDC
Inside junction box of the ET / MT-xx6:

Detail of the 24VDC connection:

Device name
|
ReaderBox-054-DC-RS232
|
HMI ET-/MT-xx6
|
Connection
|
Power supply
|
Cable
|
3 x 1 mm²
|
-
|
Designation
|
Open cable endX1
|
Terminal X1 (VDC)
|
View
|

|

|
Assignments / connections (wire / pin)
|
Wire
|
Signal
|
Pin
|
Signal
|
-
|
-
|
-
|
1
|
+24 VDC
|
1
|
|
+ VDC
|
2
|
+24 VDC
|
-
|
-
|
-
|
3
|
GND
|
2
|
|
GND
|
4
|
GND
|
PE
|
Green / yellow
|
Earth
|
PE
|
Equipotential bonding connection
|
If the X1 terminals are already being used by the optional hard disk, the power supply must be connected in an Ex-certified terminal box outside of the HMI..
If there is no internal hard disk and other devices are to be supplied with 24 VDC, the optional X12 terminal block can be used to distribute the supply voltage.
24VDC at X12 terminal block:

HMI 24VDC power supply
ReaderBox X1

|
Because Ex-e and Ex-i signal circuits must not be connected at the same time, any free terminals may only have Ex-e signal circuits connected !
|
|
X2 via RS-232
Inside junction box of the ET / MT-xx6:

RS-232 connection detail:
Device name
|
ReaderBox-...-DC(AC)-RS232*1
|
HMI ET-/MT-xx6
|
Connection
|
Data circuit
|
Cable
|
5 x 1 mm²
|
-
|
Designation
|
Open cable endX2
|
Terminal X2 (COM1 - RS-232)
|
View
|

delivery state:
all wires black and numbered..
|

|
Assignments / connections (wire / pin)
|
Wire
|
Signal
|
Pin
|
Signal
|
2
|
Blue *
|
Not used *
|
9
|
TxD
|
1
|
Brown
|
TxD
|
10
|
RxD
|
4
|
Grey *
|
Not used **
|
11
|
RTS/
|
5
|
Green / Yellow *
|
Not used **
|
12
|
CTS/
|
3
|
Black
|
GND
|
13
|
GND
|
*1)
|
DC = ReaderBox with 24 VDC connection.
AC = ReaderBox with 100 to 240 VAC connection.
|
*2)
|
The data cable X2 is multi-core cables. Any unused wires are not assigned in the ReaderBox.
The unused wires of X2 must be isolated according to applicable regulations. This may be by means of double isolation and mechanical fixing by shrink sleeving or vulcanisation. The shrink sleeving or the vulcanisation must be suitable for at least 500 V and be within the temperature parameters of the device. The shrink sleeving / vulcanisation must not be light blue. When the data cables are shortened, this must also be kept in mind.
|
|
Wire
|
Signal name
|
Definition
|
1
|
TxD
|
Data sent (out)
|
2
|
RxD
|
Data received (in)
|
3
|
GND
|
Earth (0VDC)
|
4
|
Not used
|
-
|
5
|
Not used
|
-
|
*1)
|
delivery state: all wires black and numbered.
|

|
The blue wires of the X2 data circuit of the ReaderBox is not needed and must be cut off at the cable end !
|
X2 via RS-422
Inside junction box of the ET / MT-xx6:

RS-422 connection detail:

Device name
|
ReaderBox-...-DC(AC)*1
|
Connection
|
Data circuit
|
Cable
|
5 x 1 mm²
|
-
|
Designation
|
Open cable end X2
|
Terminal X2 (COM1 - RS-232)
|
View
|

delivery state:
all wires black and numbered..
|

|
Assignments / connections
(wire / pin)
|
Wire
|
Signal
|
Pin
|
Signal
|
3
|
Black
|
RxD-b
|
1
|
TxD-b
|
4
|
Grey
|
RxD-a
|
2
|
TxD-a
|
1
|
Brown
|
TxD-b
|
3
|
RxD-b
|
2
|
Blue
|
TxD-a
|
4
|
RxD-a
|
5
|
Green / Yellow
|
Not used
|
-
|
-
|
*1)
|
DC = ReaderBox with 24 VDC connection.
AC = ReaderBox with 100 to 240 VAC connection.
|
|
|
To devices of the ET / MT-xx7 Series
24 VDC
The power supply for the xx7 series is connected to a suitable terminal block in the safe area.
Terminal assignment, electrical connection X1:

|
The output circuit cable is about 1.1 metres long and typically 3 x 1 mm² !
|
Wire
|
Signal name
|
Definition
|
*1) ...-AC-...
|
*2) ...-DC-...
|
1
|
L1
|
+ VDC
|
Supply voltage phase or 24VDC+
|
2
|
N
|
GND
|
Supply voltage neutral or earth 0VDC
|
green/yellow
|
Earth
|
|
Protective earth or equipotential bonding
|
*1)
|
Order version (100 - 240) VAC supply (ReaderBox-...-AC-...)
|
*2)
|
Order version (12 - 30) VDC supply (ReaderBox-...-DC-...)
|

|
Re. *1),
Make sure you have the AC version
before connecting the ReaderBox to the mains !
|
|
X2 via RS-232
Inside junction box of the ET / MT-xx7:

RS-232 connection detail:

Device name
|
ReaderBox-054-DC-RS232 *1
|
Connection
|
Data circuit
|
Cable
|
5 x 1 mm²
|
-
|
Designation
|
Open cable end X2
|
Terminal X97 (SER - RS-232)
|
View
|

Lieferzustand:
alle Adern schwarz und nummeriert.
|

|
Assignments / connections (wire / pin)
|
Wire *2
|
Signal
|
Pin
|
Signal
|
2
|
|
N.V.
|
1
|
TxD
|
1
|
|
TxD
|
2
|
RxD
|
4
|
|
N.V.
|
3
|
RTS/
|
5
|
Green / Yellow
|
N.V.
|
4
|
CTS/
|
3
|
|
GND
|
5
|
GND
|
*1)
|
DC = ReaderBox with 24 VDC connection.
AC = ReaderBox with 100 to 240 VAC connection.
|
*2)
|
The data cable X2 is multi-core cables. Any unused wires are not assigned in the ReaderBox.
The unused wires of X2 must be isolated according to applicable regulations. This may be by means of double isolation and mechanical fixing by shrink sleeving or vulcanisation. The shrink sleeving or the vulcanisation must be suitable for at least 500 V and be within the temperature parameters of the device. The shrink sleeving / vulcanisation must not be light blue. When the data cables are shortened, this must also be kept in mind.
|
|

|
The blue wires of the X2 data circuit of the ReaderBox is not needed and must be cut off at the cable end !
|
|